Skilled Trades
Skilled Trades — Ohm's Law, Power & NEC 80% Continuous-Load Rule
master · Skilled Trades

Ohm's Law, Power & NEC 80% Continuous-Load Rule

Licensed Electrician at work
Meet the worker
Priya Licensed Electrician
retrofit on a 1960s ranch

Priya is sizing a circuit for a new 1,500 W heater on 120 V. She must verify the breaker, the wire gauge, and that she won't trip the panel on cold mornings.

What they'll need
  • Multimeter
  • NEC ampacity chart
  • 12-AWG / 14-AWG romex
  • Breaker (15 A or 20 A)
How it's done — step by step
  1. 1

    Pick the right formula

    Volts × Amps = Watts. Solve for Amps: I = P / V = 1500 / 120 = 12.5 A.

  2. 2

    Apply the 80% rule

    Continuous loads can use only 80% of breaker. 12.5 / 0.8 = 15.6 A → use a 20 A breaker.

  3. 3

    Size the wire

    20 A circuit needs 12 AWG copper minimum (NEC Table 310.16).

  4. 4

    Verify with the meter

    After hookup, clamp meter on the hot. Reading should sit ≤ 13 A under load.

A 1500 W space heater on a 20 A / 120 V circuit. NEC 210.20(A) limits continuous loads (≥3 hr) to 80% of breaker rating. Compute draw, verify safety margin, then check what happens if the homeowner adds a 600 W toaster oven mid-shift. Wire ampacity, voltage drop on long runs, and resistive heating all interlock.

Current
12.00 A
Power
1440 W
Status
Safe

Tap Show next step to reveal the math one piece at a time.

Worked Example

1500 W heater on a 20 A circuit

Given: P = 1500 W, V = 120 V, breaker = 20 A

  1. 1

    Solve current

    I = P ÷ V = 1500 ÷ 120 = 12.5 A

Worked Example

Voltage drop trap

Given: 240 V across a 30 Ω element

  1. 1

    Find current

    I = 240 ÷ 30 = 8 A